These 2026 cases are outages in which a public cloud or cloud platform failed, or a provider facility event or account action took the customer with it. The first symptom was often latency, 404s, or a trading halt.
Azure OpenAI failed across regions on May 29, 2026 when an API-layer change made capacity errors look retriable and a Microsoft 365 retry storm overwhelmed the shared routing layer. On May 30, a separate West US 2 incident was physical: a thunderstorm and voltage instability locked out cooling and shut down compute, network, and storage in two zones. Storage checks and a telemetry backlog outlasted cooling. On August 19, Nebius lost us-central1 after a storm disabled chilled water and the building management system. Inlet temperature reached 58.5°C, and a disk hot-plug bug held Managed Kubernetes control planes down after cooling.
Supabase us-east-2 was down for 3 hours and 42 minutes from 21:12 UTC on February 12, 2026 because its own deployment enabled VPC Block Public Access. The case calls that a configuration error, not an AWS outage. Railway's nearly 10-hour outage on May 19, 2026 began when Google Cloud suspended Railway's production account, without notice, under an automated Terms of Service action. After cached routes expired, AWS and Railway Metal workloads returned 404s because edge routing still used a GCP control-plane API. Coinbase halted trading on May 7, 2026 after a datacenter thermal event aligned with an AWS thermal/facility incident. Matching-engine quorum was lost, and Kafka dependencies blocked a one-step failover.
Cases in this pattern
Networking
Supabase us-east-2 Regional Outage: Monitoring-Service Deployment Accidentally Enabled VPC Block Public Access Region-Wide
On February 12, 2026, at 21:12 UTC, Supabase suffered a 3-hour-42-minute outage in us-east-2 when a monitoring service deployment inadvertently enabled AWS VPC Block Public Access region-wide, blocking all internet gateway traffic. The investigation faced multiple red herrings: alarms triggered on shared services in a different region that were symptoms, not causes, and a lack of pre-production parity (pre-prod did not cover us-east-2) masked the blast radius. The turning point came when the team correlated timestamps of new network resource creation in us-east-2 with the exact start of the outage.Cloud Infrastructure
Railway Platform Outage: GCP Account Suspension and Multi-Cloud Control Plane Cascading Failure
Railway experienced a nearly 10-hour incident after Google Cloud incorrectly suspended its production account. While Railway runs on multi-cloud infrastructure (GCP, AWS, Railway Metal), edge proxies relied on a GCP-hosted control plane API to populate routing tables. When cached network routes expired, the outage cascaded beyond GCP, causing workloads on AWS and Metal to return 404 errors. Recovery required staged restoration of account access, persistent disks, compute instances, networking, and edge routing, with GitHub rate-limiting OAuth integrations during the recovery traffic burst.AI & Automation
Microsoft Azure OpenAI multi-region latency and failures PIR
Azure OpenAI experienced multi-region latency and failures after an upstream API change caused retry amplification from an internal Microsoft 365 workload. The investigation initially followed a credible but wrong crash signature before a second regional wave revealed the real mechanism.Cloud Infrastructure
Microsoft Azure West US 2 power and cooling PIR
A severe thunderstorm caused power disturbances across multiple datacenters in West US 2, triggering cooling lockouts and protective shutdowns across two physical availability zones. The hard part of the investigation was proving why recovery remained slow after cooling returned: storage validation and telemetry backlog had become the new bottlenecks.Cloud Infrastructure
Coinbase May 7, 2026 outage postmortem
A severe service outage interrupted trading and most customer-facing functions. The investigation had to trace a facility event through quorum loss, Kafka leader-election problems, and staged recovery blockers rather than stopping at the first platform symptom.Cloud Infrastructure
Nebius us-central1 Disruption: Storm-Induced Cooling Failure and Managed Disks Hot-Plug Recovery Bug
A storm-related event at a data center facility disabled the building management system and chilled-water cooling loop, causing data halls to overheat to a peak inlet temperature of 58.5°C within roughly two hours. Servers, network switches, and rack power systems shut down on thermal protection, triggering a region-wide outage across GPU/CPU compute, storage, Managed Kubernetes, Token Factory, and regional API/console endpoints. Recovery took significantly longer than facility cooling restoration because a region-scale cold start required manual intervention in multiple recovery paths, and a bug in the managed disks hot-plug functionality left secondary data disks unattached after instance recovery, keeping hundreds of Managed Kubernetes control planes down until a controlled mass restart was applied.Networking
Azure Multi-Region Gateway Outage: Paused Update Resumes and Overloads the Control Plane
Between 20:30 UTC on September 30 and 02:15 UTC on October 1, 2026, customers using Azure networking gateway services across 33 regions experienced intermittent failures in service management operations, and a subset of upgraded Azure ExpressRoute gateways temporarily lost on-premises connectivity; customers using Azure VMware Solution may also have temporarily lost network connectivity to their software-defined datacenter environments. The incident began when a platform-triggered gateway operating-system update that had been paused resumed across multiple regions at once, producing a surge of gateway restarts and configuration-retrieval requests against the regional gateway control plane — which was already slower per operation after an earlier change had increased processing time. Throttling and load protection were insufficient for the combined load. Restarting ExpressRoute gateway instances were marked healthy before their configuration and routing state had been fully restored, so updates proceeded to redundant instances before the first was ready; after about 30 minutes of unsuccessful configuration-retrieval attempts, the affected gateways automatically applied their locally stored last known good configurations and restored connectivity at 22:36 UTC. Microsoft paused the update, applied a configuration change in phases to restore the control plane, and rolled back the change that had slowed processing (from 01:15 UTC); the last customer impact was mitigated at 02:15 UTC, 5 hours and 45 minutes after onset.Cloud Infrastructure
Google Cloud europe-west2 London Outage: PLC Misconfiguration Blocked Generator Start After Cable Fault
On October 19, 2026 at 22:53 US/Pacific (October 20, 06:53 BST), an external underground cable fault cut primary utility feed A to the data center facility hosting Google Cloud zone europe-west2-b in London. The site was in a temporary single-feed (1N) posture because feed B's breaker had been opened on October 14 after a quarterly generator load test found issues, so feed A carried the entire critical load alone. The backup generators never started: the programmable logic controller (PLC) undervoltage sensing was wired upstream (line side) of the isolated feed B breaker, so both master PLCs sensed live voltage on a disconnected path and concluded a healthy utility source was available. The UPS batteries, providing about five minutes of runtime, carried the load until depleted, and the zone lost power entirely. Primary impact lasted 6 hours and 8 minutes; zone-scoped resources in europe-west2-b were unreachable, and the broader europe-west2 region saw transient latency and elevated errors as workloads failed over into adjacent zones.