AWS post-event summaries

AWS outage
history.

Short answer

Which major AWS outages has AWS documented?

The public AWS outage history on this page is the set of post-event summaries AWS links from its post-event summary index. AWS publishes one when an issue has broad and significant customer impact: a significant percentage of control plane API calls fail, a significant percentage of a service’s infrastructure, resources, or APIs is affected, or the issue is a total power failure or a significant network failure. Each summary states the scope, contributing factors, and actions taken, and AWS keeps it available for at least five years. The AWS Health Dashboard carries service history for the preceding 12 months. This AWS outage history lists those summaries. Each entry keeps the date, the region and services the summary names, the cause AWS stated, and the link to AWS’s own write-up.

Northern Virginia

AWS us-east-1 outage history

Later summaries call this region Northern Virginia (US-EAST-1 or us-east-1). Summaries from 2011 through 2015 say US East or US-East. The June 29, 2012 summary uses both names for one event: the title says US East Region, and the body says the US East-1 Region in Northern Virginia.

  1. Northern Virginia (us-east-1)

    Services. Amazon DynamoDB, and services that depend on it. The summary names new EC2 instance launches, Network Load Balancer, Lambda, ECS, EKS, Fargate, Amazon Connect, STS, IAM and IAM Identity Center sign-in, Redshift, and the AWS Support Center, and points to the event history for the full list.

    Cause AWS stated. Between 11:48 PM PDT on October 19 and 2:40 AM PDT on October 20, DynamoDB API error rates rose and new connections to the service failed, including connections from other AWS services. AWS states the incident was triggered by a latent defect in DynamoDB’s automated DNS management system. The root cause was a race condition that wrote an empty DNS record for dynamodb.us-east-1.amazonaws.com, which the automation failed to repair. Impact on dependents, including EC2 instance launches, continued later on October 20.

    AWS post-event summary

  2. Northern Virginia (US-EAST-1)

    Services. CloudWatch Logs, Amazon Data Firehose, the framework that publishes Amazon S3 events, Amazon ECS, AWS Lambda, Amazon Redshift, and AWS Glue. AWS attributes that impact to one internally used cell of Amazon Kinesis Data Streams. Other Kinesis cells in the region, and Kinesis in other regions, kept operating.

    Cause AWS stated. The impact ran from 2:45 PM to 9:37 PM PDT. The root cause was the cell management system’s behavior on a novel workload in that internal cell: a very large number of very low-throughput shards, which made the cell management system behave incorrectly.

    AWS post-event summary

  3. Northern Virginia (US-EAST-1)

    Services. AWS Lambda function invocations. Amazon STS, the AWS Management Console, Amazon EKS, Amazon Connect, and Amazon EventBridge saw increased error rates and latencies because Lambda invocations were degraded.

    Cause AWS stated. Errors started at 11:49 AM PDT. Invocations began returning to normal at 1:45 PM PDT, and the affected services had recovered by 3:37 PM PDT. The Lambda Frontend fleet was scaling for ordinary daily traffic and crossed a capacity threshold a single cell had not reached before. That triggered a latent software defect: execution environments were allocated for incoming requests but never fully used by the Frontend, so the cell could not provision new environments.

    AWS post-event summary

  4. Northern Virginia (US-EAST-1)

    Services. Networking devices between AWS’s internal network and the main AWS network. Running EC2 instances were unaffected. EC2 APIs used to launch or describe instances saw errors and latency, which also blocked creation of new Amazon RDS, Amazon EMR, and Amazon WorkSpaces resources. Existing Elastic Load Balancers stayed healthy, while ELB APIs slowed new provisioning and instance registration. Route 53 APIs were impaired. Existing DNS records and answers to DNS queries were not. Internal monitoring data and the ability to create support cases were also impaired.

    Cause AWS stated. At 7:30 AM PST, an automated capacity-scaling activity for a service on the main AWS network triggered unexpected behavior from many clients on the internal network. The connection surge overwhelmed the devices that join the two networks. Delays produced more retries, and the congestion persisted.

    AWS post-event summary

  5. Northern Virginia (US-EAST-1)

    Services. Amazon Kinesis, and other AWS services that use Kinesis.

    Cause AWS stated. AWS calls a small capacity addition, started at 2:44 AM PST and finished at 3:47 AM PST, the trigger and not the root cause. The new capacity caused every server in the Kinesis front-end fleet to exceed the maximum number of threads allowed by an operating system configuration. Cache construction then failed, and front-end servers were left with shard maps that could not route requests to back-end clusters.

    AWS post-event summary

  6. Northern Virginia (US-EAST-1)

    Services. Amazon S3 in the region, including GET, LIST, PUT, and DELETE. Other US-EAST-1 services that rely on S3 were affected while the S3 APIs were unavailable, including the S3 console, new EC2 instance launches, EBS volumes when data was needed from an S3 snapshot, and AWS Lambda.

    Cause AWS stated. The S3 team was debugging a billing system that was progressing more slowly than expected. At 9:37 AM PST, an authorized team member using an established playbook ran a command meant to remove a small number of servers for one subsystem used by that billing process. One input was entered incorrectly, and a larger set of servers was removed. Those servers supported the index subsystem, which holds object metadata and location, and the placement subsystem, which allocates storage for new objects. Both required a full restart, and S3 could not service requests while they restarted.

    AWS post-event summary

  7. US-East Region

    Services. Amazon DynamoDB, and some other services in the region that depend on DynamoDB.

    Cause AWS stated. At 2:19 AM PDT a brief network disruption affected a portion of DynamoDB storage servers. Membership responses from the internal metadata service took longer than the storage servers allow, so those servers removed themselves from taking requests. AWS attributes the slow responses to rapid adoption of Global Secondary Indexes, which enlarged membership lists. The metadata service did not have enough capacity for those heavier requests, and membership size was not monitored in enough detail. Simultaneous requests then exceeded the time limit, and retries added load.

    AWS post-event summary

  8. US East Region

    Services. Amazon SimpleDB. From 9:16 PM to 11:16 PM PDT, every API call was unavailable except a fraction of eventually consistent reads. CreateDomain and DeleteDomain error rates stayed elevated until 1:30 AM PDT.

    Cause AWS stated. Multiple storage nodes in one data center became unavailable together after power was lost to their servers. De-registering them suddenly increased load on SimpleDB’s lock service. Handshake latencies then exceeded the timeout, and healthy storage and metadata nodes removed themselves from the cluster.

    AWS post-event summary

  9. US-East Region

    Services. Amazon Elastic Load Balancing.

    Cause AWS stated. At 12:24 PM PST, a maintenance process was inadvertently run against production ELB state data and logically deleted a portion of it. Running load balancers kept handling requests at first, because that state was not required for basic operation. When the control plane later changed a load balancer, the missing state produced an improper configuration. Customer applications using those modified load balancers saw degraded performance and errors.

    AWS post-event summary

  10. US-East Region, one of five Availability Zones

    Services. Amazon Elastic Block Store volumes in that Availability Zone.

    Cause AWS stated. At 10:00 AM PDT, a small number of volumes slowed and some became stuck, unable to process further I/O. The root cause was a latent bug in a data-collection agent on the EBS storage servers. A collection server had been replaced after a hardware failure, but the DNS update did not reach every internal DNS server, so some storage servers kept contacting the failed collector. That path triggered a memory leak in the agent. Many servers exhausted memory together, and failover could not find enough healthy replacements.

    AWS post-event summary

  11. US East-1 Region, one Availability Zone in Northern Virginia

    Services. EC2 instances, EBS volumes, RDS instances, and ELB instances in the affected datacenter. AWS describes those resources as a single-digit percentage of the region. Control planes used to create, remove, or change resources were also degraded across the region. Unavailability of instances and volumes was limited to the affected Availability Zone.

    Cause AWS stated. The event was triggered during a large electrical storm. At 7:24 PM PDT a large voltage spike reached switching equipment in two datacenters supporting one Availability Zone. Generators in one datacenter started, and each independently failed to provide stable voltage, so they did not pick up the load. Utility power failed again at 7:57 PM PDT, and that datacenter again did not transfer to generator power. UPS batteries depleted. Servers began losing power at 8:04 PM PDT. Generator power was stabilized, restoration began at 8:14 PM PDT, and all racks had power at 8:24 PM PDT.

    AWS post-event summary

  12. US East Region, one Availability Zone

    Services. Amazon EC2 and Amazon RDS. A subset of EBS volumes in the Availability Zone could not service reads and writes, and instances using those volumes stuck with them. A portion of RDS databases in that zone became inaccessible because RDS stores databases and logs on EBS. For two periods on the first day, EBS API calls across the whole US East Region saw high error rates and latencies.

    Cause AWS stated. At 12:47 AM PDT, during a change to upgrade capacity on the primary EBS network, traffic was shifted off one redundant router. The shift was executed incorrectly: traffic went onto the lower-capacity replication network instead of the other primary router. Affected nodes lost both networks at once and were isolated from the rest of their cluster.

    AWS post-event summary

Other regions

Post-event summaries outside us-east-1

The same index includes significant events in other regions. They are part of the AWS outage history, and they use the same kind of source.

  1. Tokyo (AP-NORTHEAST-1)

    Services. AWS Direct Connect for traffic toward the Tokyo Region. Traffic between Availability Zones, internet connectivity to the Region, VPN connectivity, and Direct Connect traffic to other regions were not affected.

    Cause AWS stated. Beginning at 7:30 AM JST, customers saw intermittent connectivity problems and elevated packet loss. A subset of devices on one network layer between Direct Connect edge locations and the datacenter network failed, and the usual automation did not remove them. Disabling a newly introduced protocol restored the service by 1:42 PM JST. AWS later confirmed a latent defect in the network-device operating system, in a version that enables a protocol meant to shorten failover time. The defect requires a very specific set of packet attributes and contents. AWS states the event was triggered by customer traffic that consistently matched that signature, and that AWS has no reason to suspect malicious intent.

    AWS post-event summary

  2. Tokyo (AP-NORTHEAST-1), part of a single Availability Zone

    Services. Amazon EC2 and Amazon EBS in the affected area. RDS, Redshift, ElastiCache, and WorkSpaces in that Availability Zone were affected where their underlying EC2 instances were. EC2 instances and EBS volumes in the region’s other Availability Zones were not.

    Cause AWS stated. Beginning at 12:36 PM JST, a small percentage of EC2 servers shut down from overheating. A datacenter control system failed, and multiple redundant cooling systems failed in parts of the zone. During failover away from one control host, a bug in third-party control-system logic made the control system unresponsive. In a small portion of the datacenter, cooling did not enter its designed maximum-cooling mode and shut down. Purge mode also failed. Programmable logic controllers for some air handlers were unresponsive and had to be reset. The affected cooling systems were restored at 3:21 PM JST.

    AWS post-event summary

  3. Seoul (AP-NORTHEAST-2)

    Services. DNS resolution for EC2 instances. EC2 network connectivity, and DNS resolution outside EC2 instances, were not affected.

    Cause AWS stated. Between 8:19 AM and 9:43 AM KST, the number of healthy hosts in the EC2 DNS resolver fleet fell. The root cause was a configuration update that incorrectly removed the setting for the minimum number of healthy hosts. The fleet treated that minimum as a very low default, and DNS queries from inside EC2 instances began to fail. Service returned when the number of healthy hosts was restored to its previous level.

    AWS post-event summary

  4. Sydney Region, one Availability Zone

    Services. EC2 instances that lost power in one facility in that Availability Zone.

    Cause AWS stated. At 10:25 PM PDT the utility provider lost power at a regional substation during severe weather, and multiple AWS facilities lost utility power. In one facility the power redundancy did not work as designed. The utility failure was an unusually long voltage sag. Breakers that isolate the diesel rotary UPS from utility power did not open quickly enough, the stored energy drained into the degraded grid, and generators that had started could not be connected to the racks. On-site technicians restored power at 11:46 PM PDT.

    AWS post-event summary

  5. EU West Region, a significant portion of one Availability Zone

    Services. Amazon EC2, Amazon EBS, and Amazon RDS. Almost all EC2 instances and 58% of the EBS volumes in that Availability Zone lost power, as did the networking gear connecting the zone to the internet and to the region’s other zones.

    Cause AWS stated. The disruption began at 10:41 AM PDT when the utility provider’s 110kV, 10 megawatt transformer failed. The utility’s first diagnosis was a lightning strike. The utility later believed it was not a lightning strike and was still investigating the root cause. One programmable logic controller did not bring a portion of the backup generators online. From the state of that controller, AWS believed it had detected a large ground fault and then failed to finish the connection. With utility power gone and those generators offline, UPS batteries drained.

    AWS post-event summary

  6. South America (SA-EAST-1)

    Services. Resources in one Availability Zone that lost power. Both Availability Zones in the region then had degraded internet connectivity for 20 minutes.

    Cause AWS stated. At 10:05 PM PST the zone lost utility power because of a fault at the local utility’s substation and switched to generators. A breaker in front of one generator opened, a second generator failed mechanically, and the remaining generators shut down under the extra load. The control system that aggregates generator power did not function properly. The facilities team bypassed it and brought generators online manually. During network recovery, a technician brought a device up manually with a bad configuration. The device advertised an invalid route, which degraded internet connectivity for both Availability Zones until it was taken out of service.

    AWS post-event summary

The index these entries were taken from is AWS’s post-event summary page. A summary AWS publishes later is a new primary source. It is not inferred from news coverage.

Lessons

How to read one of these summaries

A post-event summary is the provider’s incident postmortem: the record written after impact, with the scope, the contributing factors, and what changed. A status update during the event is a different document. The troubleshooting field guide is the method for reading either one: keep the trigger separate from the mechanism, and keep a failed first explanation in the timeline.

The November 25, 2020 Kinesis summary is the pattern. AWS names the capacity addition as the trigger, and the operating-system thread limit as the root cause. The February 28, 2017 S3 summary separates an incorrect command input from the two subsystems that then had to restart.

A failure that customers see from inside an AWS region can still be their own change. Supabase’s February 12, 2026 us-east-2 case records a monitoring deployment that enabled region-wide VPC Block Public Access. The source report calls that a pipeline configuration error.

Workloads running on AWS can also fail because a control plane somewhere else stops. Railway’s May 19, 2026 case begins with a Google Cloud account suspension. After cached routes expired, workloads on AWS returned 404s because edge routing still called a control-plane API hosted on Google Cloud.

Coinbase’s May 7, 2026 case follows a facility event through matching-engine quorum loss, then through the Kafka-related dependencies that still blocked trading after quorum returned. The case record ties the start of customer impact to an AWS thermal event in Coinbase’s account. That date is not on AWS’s post-event summary index, so it is not an entry above.

Power and cooling events of the kind in the timeline are grouped with other public cases on the cooling and power topic. Reported facts in those cases stay with the cited source.

Direct answers

Questions about AWS outage history

What is the AWS outage history?

The public AWS outage history on this page is the set of post-event summaries AWS links from its post-event summary index. AWS publishes one when an issue has broad and significant customer impact: a significant percentage of control plane API calls fail, a significant percentage of a service’s infrastructure, resources, or APIs is affected, or the issue is a total power failure or a significant network failure. Each summary states the scope, contributing factors, and actions taken, and AWS keeps it available for at least five years. The AWS Health Dashboard carries service history for the preceding 12 months.

What is the AWS us-east-1 outage history?

The AWS us-east-1 outage history in AWS’s own post-event summaries is: October 19, 2025 (Amazon DynamoDB); July 30, 2024 (CloudWatch Logs, Amazon Data Firehose, the framework that publishes Amazon S3 events, Amazon ECS, AWS Lambda, Amazon Redshift, and AWS Glue); June 13, 2023 (AWS Lambda function invocations); December 7, 2021 (Networking devices between AWS’s internal network and the main AWS network); November 25, 2020 (Amazon Kinesis, and other AWS services that use Kinesis); February 28, 2017 (Amazon S3 in the region, including GET, LIST, PUT, and DELETE); September 20, 2015 (Amazon DynamoDB, and some other services in the region that depend on DynamoDB); June 13, 2014 (Amazon SimpleDB); December 24, 2012 (Amazon Elastic Load Balancing); October 22, 2012 (Amazon Elastic Block Store volumes in that Availability Zone); June 29, 2012 (EC2 instances, EBS volumes, RDS instances, and ELB instances in the affected datacenter); April 21, 2011 (Amazon EC2 and Amazon RDS).

Where does AWS publish the cause of an outage?

AWS publishes the cause in the post-event summary for that event. The summaries are linked from aws.amazon.com/premiumsupport/technology/pes/. A status update during the incident reports the live state. The summary is the later record of scope, contributing factors, and what AWS changed.